Product Description Technical Parameter Genset model YC1200GF YC1350GF YC1500GF YC1700GF YC1800GF Prime power (KW/kVA) 1200/1500 1350/1688 1500/1875 1700/2125 1800/2250 Standby power (KW/kVA) 1350/1688 1500/1875 1650/2062 1800/2250 2000/250






| Technical Parameter | ||||||
| Genset model | YC1200GF | YC1350GF | YC1500GF | YC1700GF | YC1800GF | |
| Prime power (KW/kVA) | 1200/1500 | 1350/1688 | 1500/1875 | 1700/2125 | 1800/2250 | |
| Standby power (KW/kVA) | 1350/1688 | 1500/1875 | 1650/2062 | 1800/2250 | 2000/2500 | |
| Rated voltage V | 400/230 | |||||
| Rated currency A | 2180 | 2450 | 2725 | 3067.3 | 3247.7 | |
| Frequency | 50 | |||||
| Power factor | 0.8 | |||||
| Frequency drop % | ≤2 | |||||
| Steady state frequency band | ≤0.5 | |||||
| (For rated frequency) Transient frequency deviation % | 100%The sudden | ≤+10 | ||||
| reduction power | ||||||
| Sudden load power | ≤-7 | |||||
| Recovery frequency time ( s ) | ≤3 | |||||
| Steady state voltage deviation % | ≤±1 | |||||
| Transient voltage | 100%The sudden | ≤+20 | ||||
| deviation% | reduction power | |||||
| Sudden load power | ≤-15 | |||||
| Voltage recovery time ( S ) | ≤3 | |||||
| Voltage unbalance degree % | ≤1 | |||||
| Genset dimension(mm) | 6000*2500*3080 | 6000*2500*3080 | 6000*2500*3080 | 6300*2500*3080 | 6800*2500*3080 | |
| /Weight (kg) | /13600 | /14600 | /14800 | /16500 | /197000 | |
| Engine | Model | YC12VC2070-D31 | YC12VC2270-D31 | YC12VC2510-D31 | YC12VC2700-D31 | YC12VC3000-D30 |
| Prime power(KW) | 1380 | 1520 | 1680 | 1805 | 2005 | |
| Standby power(KW) | 1520 | 1670 | 1850 | 1985 | 2206 | |
| Brand/manufacture | YUCHAI | |||||
| Speed(r/min) | 1500 | |||||
| No. of Cylinder | 12 | |||||
| Cylinder arrangement | V | |||||
| Stroke | Four stroke | |||||
| Air intake mode | Turbocharged & Intercooled | |||||
| Fuel supply | Electrical regulation | |||||
| Bore x stroke | 200×210mm | |||||
| Displacement | 79.17L | |||||
| Emission | No-road T3 | |||||